Technical data - Armaflex Protect
Brief description: Flexible fire protection bulkheading and insulation for non-combustible, combustible pipelines and combustible pipelines for gases (R 30 - R 90) running through fire-resistant walls and ceilings.
Type of material: elastomeric foam based on synthetic rubber
Color: black
Applications: Fire protection bulkheading and insulation for heating, sanitary and refrigeration piping up to 326 mm outer diameter and combustible pipingup to 75 mm outer diameter.
Special features: For detailed information on application areas (construction elements, application range, size restrictions) and a construction description of the bulkhead, please refer to the Armaflex Protect installation instructions.
Notes: The declaration of performance is available on our homepage in accordance with Article 7(3) of EU Regulation No. 305/2011: www.armacell.com/DoP"
Property |
Value/assessment
|
Test certificate*1 |
Monitoring*2 |
Special Notes |
application range |
-50 °C - 85°C
|
EU 5925 |
?/? |
Testing according to EN 14706, EN 14707 and EN 14304 |
Thermal conductivity |
λ ≤ 0,056 W/(m * K)
|
EU 5925 |
?/? |
Testing according to EN 12667 EN ISO 8497 |
Water vapor diffusion resistance |
μ ≥ 7.000
|
EU 5925 |
?/? |
Testing according to EN 12086 and EN 13469 |
Building material class |
EL
|
EU 5925 |
?/? |
Classified according to EN 13501-1T ested according to EN ISO 11925-2 |
Practical Fire Behavior |
Self-extinguishing, non-dripping, does not conduct fire. |
|
|
|
Component fire resistance |
R30 - R90 |
D 4226 D 4305
|
?/? |
Testing according to DIN 4102-11 |
UV resistance |
Protection against UV radiation required |
|
|
|
Storage and shelf life |
Cartons must be stored horizontally |
|
|
Can be stored in dry, clean rooms at normal relative humidity (50-70 %) and ambient temperature (0-35 °C). The minimum transport temperature is 50 °C under the condition of frost-free storage before installation. |
1. Bei Applications with UV exposure Armaflex must be protected with a sheathing within 3 days.
*1 Further documents such as test certificates, approvals and the like can be requested by quoting the specified registration number.
*2 ?: official monitoring by independent institutes and/or testing authorities.
?: Factory production Control